7.4
A 24 V– / 2 A Output Module
Function
Connection
7.5

AR/2A Relay Output module

1070 072 145-102 (01.07) GB
The general conditions and specifications appearing in section 7.1 apply.
The outputs are short-circuit protected. The electronic short-circuit protec-
tion is triggered by a current of typically 2.4 A. Due to thermal load considera-
tions, output loads must not exceed the rated 2 A current.
Output parallelling is not permitted.
There is no electrical connection between the A-outputs and B-outputs on
the module. With the prerequisite of having two separate power supplies,
this facilitates the separate shutdown of the supply voltage for the A-outputs
while the B-outputs remain functional (in an "Emergency–STOP" situation,
for example). The output circuit diagram is shown below.
The general conditions and specifications appearing in section 7.1 apply.
Digital Output Modules
24 V_A
Out_A
0 V_A
24 V_B
Out_B
0 V_B