A 24 V- Output Module / 0.5 A (16-Way And 32-Way) - Bosch CL200 User Manual

Table of Contents

Advertisement

7.3
A 24 V– Output Module / 0.5 A (16-way and 32-way)
Function
Connection
1070 072 145-102 (01.07) GB
The general conditions and specifications appearing in section 7.1 apply.
The outputs are short-circuit protected. The electronic short-circuit protec-
tion is triggered by a current of typically 1.2 A. Due to thermal load considera-
tions, output loads must not exceed the rated 0.5 A current.
Multiple overloads have no effect because each individual output is overload
protected.
The outputs are electronically protected when switching off inductive loads.
The voltage peaks are limited to the following values:
D On the A 24 V- / 0.5 A (16-way), to typically –18 V.
D On the A 24 V- / 0.5 A (32-way), to typically – 26 V.
The output module designated A 24 V– / 0.5 A (32-way) differs from the com-
panion model A 24 V– / 0.5 A (16-way) in the following:
D Number of digital outputs: 32
D Power supply to the outputs is individual and word-wise.
D Connecting terminals use the 3.5 mm form factor vs. 5.08 mm.
Output parallelling:
D On the output module A 24 V– / 0.5 A featuring 32 digital outputs, it is pos-
sible to parallel-switch 4 outputs per nibble, with a total current of 2 A.
D On the output module A 24 V– / 0.5 A featuring 16 digital outputs, two out-
puts in each of the areas listed below can be paralleled with a total current
of 1 A:
D X11A0 through X11A3
D X11A4 through X11A7
D X12B0 through X12B3
D X12B4 through X12B7
D At the same time, the respective outputs must also receive a control si-
gnal from the PLC program.
Digital Output Modules