Central Processing Unit
5–18
Specifications
Analog output,
as per EN 61131-2
Power output, voltage rated
D Voltage range
D Load resistance
D Short-circuit current
Power output, current rated
D Current range
D Load resistance
Output impedance within signal range
D Current rated
D Voltage rated
Isolation potential
Settling time, full amplitude
Overshoot
Conversion time
Digital display
Resolution
Value of LSB (w/o standardization)
Value of LSB (w/ standardization)
Temperature coefficient
Monoticity
Non-linearity
Repeat accuracy
Output ripple
Short–term deviation during
pulse shaped interference
Cable length
The output of analog values always occurs with the next exchange of the I/O
image.
System area
S82 / S83
Analog output
1
D 0 to 10 V
D Standardizable to
between 2 and 10 V via OM2
w 1 kW
32 mA
D 0 to 20 mA
D Standardizable to
between 4 and 20 mA via OM2
v 600 W
11.6 kW
24.9 kW
No isolation
< 2 ms
No overshoot
Cycle time plus 16 ms
16 bit, straight binary
12 bit
12
D 10 V : 2
= 2.4 mV
12
D 20 mA : 2
= 4.9 mA
12
D 8 V : 2
= 2.0 mV
12
D 16 mA : 2
= 3.9 mA
1 %, 5 to 55 _C
Yes
< "1 LSB
> 99 %
< 100 mV
SS
≤ 2 % (Deviations are below 2 % in a
normal industrial environment. In ex-
treme interference conditions spora-
dic deviations in excess of 2 % may
occur.)
max. 100 m, screened
Analog output
Channel 0
1070 072 145-102 (01.07) GB