Vertical module rack installation
1070 072 145-102 (01.07) GB
The vertical arrangement of the CL200 is permissible only in a single-row
configuration. The following restrictions must be observed:
D The maximum permitted configuration is two module racks.
D CPU and power supply module always to occupy bottom slots.
100 + Cable
channel
.
When using vertical installation, the permissible operating tempera-
ture as per EN 61131-2 is reduced to between 5 and 40 _C, and only 50%
of the outputs may have a HIGH signal applied at the same time.
ZE200
NT200
Maximum expansion,
Basic unit plus 1 expansion unit
Clear space
100 +Cable
100 +Cable
channel
channel
Module Racks
3–13