Setting The Reset Point (B.rsp); Setting The Switching Difference (Hysteresis) (B.hys) - JUMO DELOS SI Operating Manual

Electronic pressure switch with display. b 40.5052.0
Hide thumbs Also See for DELOS SI:
Table of Contents

Advertisement

7 Commissioning

7.12 Setting the reset point (B.RSP)

Setting

7.13 Setting the switching difference (hysteresis) (B.HYS)

Setting
40
See section 7.10 "Setting the switching function (B.Fct)", page 37.
Setting range:
Factory setting:
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "B.RSP".
"Press"
Enter the value "digit by digit."
See section 7.10 "Setting the switching function (B.Fct)", page 37.
Setting range:
Factory setting:
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "B.HYS".
"Press"
Enter the value "digit by digit."
0 to 100% of the nominal measuring range
40% of the nominal measuring range
0 to 100% of the nominal measuring range
40% of the nominal measuring range
"-" Flashing
Continuous
"-" Flashing
Continuous