7.10 Setting the switching function (B.Fct)

General
7.10.1 Hysteresis
Relay behavior
Setting
Example
3.40nA =
22nA =
The response of the instrument's switching output can be selected:
- Hysteresis make contact
- Hysteresis break contact
- Window function make contact
- Window function break contact
p
(1)
SP
Switching point
(2)
RSP
Reset point
(3)
Hysteresis
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
For underrange
error signal = 0 mA for measuring range 0 ... 20 mA
error signal = 3.4 mA for measuring range 4 ... 20 mA
error signal = 0 V for measuring range 0 ... 10 V
For overrange
error signal = 22 mA for measuring range 0 ... 20 mA
error signal = 22 mA for measuring range 4 ... 20 mA
error signal = 10.7 V for measuring range 0 ... 10 V
1
1
1
0
0
1
1
0
0
(4)
(5)
7 Commissioning
3
2
t
1
4
0
1
5
0
no
SPST (make)
nc
SPST (break)
37