Parameter - JUMO DELOS SI Operating Manual

Electronic pressure switch with display. b 40.5052.0
Hide thumbs Also See for DELOS SI:
Table of Contents

Advertisement

6.4

Parameter

6.4.1 Input
Parameter
Pressure unit
Offset
(zero-point correction)
Damping
(filter time constant)
6.4.2 Analog output
Parameter
Signal type
(for analog output)
Scaling start
(for analog output)
Scaling end
(for analog output)
Signal for error
(for analog output)
1
The default setting is marked in bold.
Display
Setting range
bar
kPa
MPa
psi
mbar
Note:
The units kPa and mbar cannot be configured for
all measuring ranges.
-20.00 ... 0.00 ... +20.00% of the measuring range
Note:
Automatic offset correction See section 7.5
"Setting the zero point (offset) (Off.P)", page 31.
0.00 ... 99.99 s
Display
Setting range
4 ... 20 mA
0 ... 20 mA
0 ... 10 V
0.00 ... 75.00% of nominal measuring range
25.00 ... 100% of nominal measuring range
3.4 mA or 22 mA for output signal 4...20 mA
0 mA or 22 mA for output signal 0...20 mA
0 V or 10.7 V for output signal 0...10 V
Note:
Depending on the configured output signal.
6 Operation
1
1
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

405052