JUMO DELOS SI
Electronic Pressure Switch with Display
B 40.5052.0
Operating Manual
2009-06-15/00526948

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DELOS SI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for JUMO DELOS SI

  • Page 1 JUMO DELOS SI Electronic Pressure Switch with Display B 40.5052.0 Operating Manual 2009-06-15/00526948...
  • Page 3: Table Of Contents

    Contents Typographical conventions ............5 Warning signs ....................5 Note signs ....................5 Description ................6 General ......................6 Identifying the instrument version ........... 7 Nameplate ....................7 Block diagram ....................7 Type description ..................8 Accessories ....................10 Electrical connection .............. 11 Installation instructions ................11 Color assignment of M12 x 1 round plug ..........11 Terminal assignment for output 470 ............12 Terminal assignment for output 471 ............12 Terminal assignment for outputs 475, 476, and 477 .........13...
  • Page 4 Contents Commissioning ............... 26 Getting started ...................26 Unlocking the instrument (code entry) ............27 Cancel operation ..................28 Selecting the unit of the measured value (Uni.P) ........28 Setting the zero point (offset) (Off.P) ............31 Setting the filter time constant (damping) (DamP) ........32 Setting the output signal (S.TyP) ..............32 Setting scaling ....................33 Setting the error signal (S.Err) ..............36...
  • Page 5: Typographical Conventions

    1 Typographical conventions Warning signs Danger This symbol is used when there may be danger to personnel if the instructions are ignored or not followed correctly! Caution This symbol is used when there may be damage to equipment or data if the instructions are ignored or not followed correctly! Caution This symbol is used where special care is required when handling components...
  • Page 6: Description

    2 Description General Depending on its design, the instrument measures relative or absolute pressure in liquid and gaseous media. The pressure is displayed digitally. Depending on the design, the following outputs are available: - 1 PNP switching output - 2 PNP switching outputs - 1 PNP switching output + 1 analog output 4 ...
  • Page 7: Identifying The Instrument Version

    3 Identifying the instrument version Nameplate on the pressure switch Made in Germany www.jumo.net DELOS SI 405052/000 TN 12345678 0...250 mbar DC 12...30 V 4...20 mA/OC: 250 mA F.-Nr.: 001234567801008350123 Type Output signal Part number Manufacturing number Measuring range Date of manufacture...
  • Page 8: Type Description

    3 Identifying the instrument version Type description (1) Basic type 405052 JUMO DELOS SI Electronic Pressure Switch with Display (2) Basic type extension None For elevated medium temperatures up to 200°C Special design (3) Nominal (rated) measuring range Measuring range - pressure 0 ...
  • Page 9 Clamp to DIN 32 676, DN25 Clamp to DIN 32 676, DN50 Small flange connection Tank connection with groove union nut , DN25 JUMO PEKA (EHEDG-certified) Suitable for connecting to pressure measuring instrument (6) Process connection material Stainless steel 316L (7) Electrical connection...
  • Page 10: Accessories

    3 Identifying the instrument version Accessories Sales No. Designation 40/00404585 4-pin cable connector (straight) M 12 x 1 with 2-m PVC cable 40/00409334 4-pin angle box M 12 x1 with 2-m PVC cable 40/00522384 Setup program 40/00507861 Connecting cable (only required for programming with the setup program) 70/00456352 PC interface line including USB/TTL converter and adapter (USB connecting cable)
  • Page 11: Electrical Connection

    4 Electrical connection Installation instructions The electrical connection must only be performed by qualified personnel! The load circuits must be fused for the maximum load currents in each case to prevent the instrument from being destroyed. Electromagnetic compatibility meets the requirements of EN 61326, No other consumers can be connected to the power supply of the instrument.
  • Page 12: Terminal Assignment For Output 470

    4 Electrical connection Terminal assignment for output 470 One PNP switching output Power supply voltage 1 L+ 12 ... 30 V DC 3 L- Output 4 K1 Highside Open Collector maximum 0.25 A Interface Terminal assignment for output 471 Two PNP switching outputs Power supply voltage 1 L+ 12 ...
  • Page 13: Terminal Assignment For Outputs 475, 476, And 477

    4 Electrical connection Terminal assignment for outputs 475, 476, and 477 One PNP switching output + one analog output Power supply voltage 1 L+ 12 ... 30 V DC 3 L- Output 4 K1 Highside Open Collector maximum 0.25 A 2 Analog 0(4)...20 mA / 0...10 V Interface...
  • Page 14: Mounting

    5 Mounting General information The compatibility of the instrument with the measuring medium must be tested, See section 11.1 "Technical data", page 49. Mounting - Find a location that ensures easy accessibility for later operation. location - The fastening must be secure and must ensure low vibration for the instrument.
  • Page 15 5 Mounting 5.1.2 Rotating the housing The instrument housing can be rotated a maximum of 320° with the combination tool (1). 320° max.
  • Page 16: Dimensions Of Electronic Pressure Switches

    5 Mounting Dimensions of electronic pressure switches ø42 Type 405052/000-... Type 405052/004-... The overall height is 40 mm greater for instruments with basic type extension 004 (for increased medium temperature up to 200°C). See drawing...
  • Page 17: Dimensions Of Process Connections, Not Front-Flush

    5 Mounting Dimensions of process connections, not front-flush 1/4-18 NPT 11.07 G1/2 G1/2 1/4-18 NPT ø7 G1/2 G1/4 ø27 ø19 G1/4 G1/2 A = Profile seal DN G3/4 B = Profile seal DN G1/2 E = SW 27 F = SW 32...
  • Page 18: Dimensions Of Process Connections, Front-Flush

    5 Mounting Dimensions of process connections, front-flush G3/4 ø24 G3/4 G3/4 G3/4 ø24.5 ø30 30.5 A = profile seal DN G3/4 D = Drill out after tapping B = profile seal DN G1 F = SW 32 C = O-ring 26.7 x 1.78 G = SW 41...
  • Page 19 5 Mounting 603 to 607 Process ø D1 ø D2 ø D3 ø D4 connection 36.5 RD 44 x 1/6 RD 52 x 1/6 RD 65 x 1/6 68.5 RD 78 x 1/6 612 to 616 Process Nominal Size ø D1 ø...
  • Page 20 5 Mounting ø19 ø26 ø40 RD52 x 1/6 E = SW 27 Process connection 997 is EHEDG-certified For detailed information about this process connection system, see data sheet 40.9711.
  • Page 21: Operation

    6 Operation Controls (1) Protective screw (2) Hexagon socket Unscrew the protective screw (1). "Turn / push" the control element (2) with the enclosed combination tool (or a 0.5x3 screwdriver). LC display 6.2.1 Measurement mode (normal display) Example: The display is lit yellow.
  • Page 22: Levels

    6 Operation 6.2.2 Settingmode Example: The display is lit red. Operation Press the combination tool less than 1 second ( < 1 s) Continue Press the combination tool less than 1 second ( < 1 s) Yes (accept) Press the combination tool more than 3 seconds ( > 3 s) No (Cancel) No activity for more than 60 seconds ( >60 s) Timeout...
  • Page 23: Parameter

    6 Operation Parameter 6.4.1 Input Parameter Display Setting range Pressure unit mbar Note: The units kPa and mbar cannot be configured for all measuring ranges. Offset -20.00 ... 0.00 ... +20.00% of the measuring range (zero-point correction) Note: Automatic offset correction See section 7.5 "Setting the zero point (offset) (Off.P)", page 31.
  • Page 24 6 Operation 6.4.3 Binary output 1 Parameter Display Setting range Switching function Hysteresis, make contact (for switching output only) Hysteresis, break contact Window, make contact Window, break contact See section 7.10 "Setting the switching function (B.Fct)", page 37. Switching point 0.00 ...
  • Page 25: Display And Operation

    6 Operation Parameter Display Setting range Switching delay 0.00 ... 99.99 s (for second switching See section 7.10 "Setting the switching function output only) (B.Fct)", page 37. 6.4.5 Display and operation Parameter Display Setting range Display position Normal (for normal operation) Rotated (for overhead operation) See section 7.15 "Setting the display alignment (D.Dir)", page 41.
  • Page 26: Commissioning

    7 Commissioning Getting started This is a suggestion for configuring the instrument reliably in little time. By checking the setting options of this list before starting the configuration, you can avoid timeouts during the configuration. Mounting the instrument, See section 5 "Mounting", page 14. Installing the instrument, See section 4 "Electrical connection", page 11.
  • Page 27: Unlocking The Instrument (Code Entry)

    7 Commissioning Unlocking the instrument (code entry) The instrument is protected by a code to prevent unauthorized operation. The code is set to 0072 in the factory. It can only be changed with the setup program. If the code is set to 0000 with the setup program, the instrument is unprotected.
  • Page 28: Cancel Operation

    7 Commissioning parameter level. After an incorrect code is entered: Cancel operation Press and hold the combination tool (2) longer than 3 seconds or wait for timeout (no activity for longer than 60 seconds). Selecting the unit of the measured value (Uni.P) Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27.
  • Page 29 7 Commissioning "Rotate" The measured pressure is shown in Kilopascal. "Rotate" The measured pressure is shown in Megapascal (MPa). "Rotate" The measured pressure is shown in psi. To confirm setting: "Press" until the display is no longer flashing.
  • Page 30 7 Commissioning 7.4.1 Display and setting options of the instrument Display Measuring range Unit Start mbar -400.0 400.0 -0.400 0.400 -0.4 ... 0.4 bar -40.00 40.00 -0.040 0.040 -5.802 5.802 mbar -1000 3000 -1.000 3.000 -1 ... 3 bar -100.0 300.0 -0.100 0.300...
  • Page 31: Setting The Zero Point (Offset) (Off.p)

    7 Commissioning Setting the zero point (offset) (Off.P) 7.5.1 Automatic offset adjustment This setting is used to accept the current measured value as the new zero point. Automatic offset adjustment is only possible for instruments with a relative pressure measuring range! Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27.
  • Page 32: Setting The Filter Time Constant (Damping) (Damp)

    7 Commissioning Setting the filter time constant (damping) (DamP) The filter time constant (damping) can be used to smooth the measured value. Small filter time constant: the display is refreshed quickly. Large filter time constant: Display refresh is slower. The value is entered in seconds with two places after the decimal. Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27.
  • Page 33: Setting Scaling

    7 Commissioning Setting scaling Customer- The customer measuring range (2) is defined by: specific - Range start (4) measuring - Range end (5) range - Span (MSP) Example Actual The instrument has a nominal measuring range (1) from 0 to 4 bar Target The customer would like to measure the pressure in the range from 1 to 2 bar (25% of the nominal measuring range).
  • Page 34 7 Commissioning Example Actual The instrument has a nominal measuring range (1) from 0 to 4 bar and the instrument has an output signal from 4 to 20 mA (3). Target The customer would like: the "Customer measuring range" (2) from 1 to 2 bar (25% of nominal measuring range (1) should correspond to the output signal from 4 to 20 mA (100%).
  • Page 35 7 Commissioning 7.8.1 Setting the starting value of scaling (Sc.Lo) The output signal can only be scaled for instruments with analog output! Setting range: 0 to 75% of the nominal measuring range Factory setting: Initial value of measuring range Example The instrument has a nominal measuring range -400 ...
  • Page 36: Setting The Error Signal (S.err)

    7 Commissioning 7.8.2 Setting the final value of scaling (Sc.Hi) The output signal can only be scaled for instruments with analog output! Explanation See section 7.8.1 "Setting the starting value of scaling (Sc.Lo)", page 35. Setting range: 25 to 100% of the nominal measuring range Factory setting: Final value of measuring range Setting...
  • Page 37: Setting The Switching Function (B.fct)

    7 Commissioning Example 3.40nA = For underrange error signal = 0 mA for measuring range 0 ... 20 mA error signal = 3.4 mA for measuring range 4 ... 20 mA error signal = 0 V for measuring range 0 ... 10 V 22nA = For overrange error signal = 22 mA for measuring range 0 ...
  • Page 38 7 Commissioning "Rotate" until the bottom line shows "B.Fct". "Press" B.RSp B.Sp 0 = Hysteresis of make contact (switching difference) (factory setting) B.RSp B.Sp 1 = Hysteresis of break contact (switching difference) = min. contact 7.10.2 Window Relay response Switching point SPST (make) Reset point SPST (break)
  • Page 39: Setting The Switching Point (B.sp)

    7 Commissioning 2 = Window function make contact B.Hys B.Hys B.RSp B.Sp 3 = Window function break contact B.Hys B.Hys B.RSp B.Sp 7.11 Setting the switching point (B.SP) See section 7.10 "Setting the switching function (B.Fct)", page 37. Setting range: 0 to 100% of the nominal measuring range Factory setting: 50% of the nominal measuring range...
  • Page 40: Setting The Reset Point (B.rsp)

    7 Commissioning 7.12 Setting the reset point (B.RSP) See section 7.10 "Setting the switching function (B.Fct)", page 37. Setting range: 0 to 100% of the nominal measuring range Factory setting: 40% of the nominal measuring range Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27.
  • Page 41: Setting The Switching Delay (B.dly)

    7 Commissioning 7.14 Setting the switching delay (B.DLY) Setting range: 0.00 to 99.99 s Factory setting: 0.00 s Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27. "Rotate" until the bottom line shows "B.DLY". "Press" "0"...
  • Page 42: Setting The Display Unit (D.uni)

    7 Commissioning 7.16 Setting the display unit (D.Uni) Setting range: Uni.P = pressure unit set as for "Uni.P", See section 7.4 "Selecting the unit of the measured value (Uni.P)", page Pro2 = percentage of scaled measuring range = "Sc.Hi" minus "Sc.Lo", See section 7.8.1 "Setting the starting value of scaling (Sc.Lo)", page 35 and See section 7.8.2 "Setting the final value of scaling (Sc.Hi)", page 36.
  • Page 43: Displaying The Version Of The Operating Device Software (Sw.di)

    7 Commissioning 7.17 Displaying the version of the operating device software (SW.Di) Setting range: Read only Factory setting: Setting Unlock the instrument, See section 7.2 "Unlocking the instrument (code entry)", page 27. "Rotate" until the bottom line shows "SW.Di". "Press" "Alternating"...
  • Page 44: Calibration

    8 Calibration Setting the zero point (offset) 8.1.1 Automatic offset adjustment Automatic offset adjustment is only possible for instruments with a relative pressure measuring range! On the instrument See section 7.5.1 "Automatic offset adjustment", page 31. By setup program not possible. 8.1.2 Edited offset setting On the instrument See section 7.5.2 "Edited offset setting", page 31.
  • Page 45: Setup Program

    9 Setup program Function Configurable The optionally available PC setup software (TN 20/00522384) can be used to parameters operate the instrument conveniently from a PC. Depending on the device design, the following settings are possible, for example: - Measuring range and limits of measuring range. - Response of outputs when the measuring range is exceeded.
  • Page 46: Start The Setup Program

    Connect the PC interface line (gray) (c) to the notebook (4). Connect the cable (a) to the power supply (1) and connecting cable (b). Start the setup program Start / Programs / JUMO instruments / Setup program JUMO DELOS K, SI,...
  • Page 47 9 Setup program...
  • Page 48: Eliminating Errors And Faults

    10 Eliminating errors and faults 10.1 Possible errors Display Possible cause Measure - Overrange or Configure other measuring range, underrange Chapter 7.4 "Selecting the unit of the measured value (Uni.P)". - Broken sensor. Device error: 1), 6), 7), 8): Call Customer Service; see the back of the Operating - 1 = Internal communication Manual.
  • Page 49: Instrument Description

    11 Instrument description 11.1 Technical data General Reference conditions DIN 16086 and EN 60770 Sensor system Construction Silicon sensor with stainless steel separating diaphragm Pressure transfer Synthetic oil, FDA-compliant medium more than 10 million Permissible load change Location Mounting location Calibration location Device standing vertically, process connection on bottom Location-dependent...
  • Page 50 11 Instrument description Input All measuring ranges can be overloaded to -1 bar (vacuum-proof) Relative pressure Measuring range Overload capacity 1.6 Bursting pressure Measuring range -0.4...0.4 -1...1 -1...3 -1...9 -1...24 Overload capacity 1.6 Bursting pressure Absolute pressure Measuring range Overload capacity 1.6 Bursting pressure Outputs Analog output...
  • Page 51 All flange connections are welded and therefore have no seals - Process connection FPM standard 521, 523, 571, 575, 576, 652 - Process connection FPM, VMQ (silicon), EPDM also available, see Data Sheet 40.9711 997 (JUMO PEKA) Measurement diaphragm Stainless steel 316L Material Ra ≤ 0.8 µm Surface...
  • Page 52 11 Instrument description Ambient conditions Permissible temperatures Measuring material -25 ... +100°C (+135°C max. 1 hour per day) - for basic type -25 ... +200°C extension 004 Environment -25 ... +75°C - Ambient Restricted function: Stationary use only, danger of broken cable, temperature -50°C display does not function Storage...
  • Page 53 11 Instrument description Accuracy Relative pressure Nominal (rated) measuring range Linearity 0.15 0.15 % of end val. of nom. mess. range Accuracy at 0.35 0.25 0.25 0.25 0.25 % of end val. of +20°C nom. mess. range Accuracy at % of end val. of -20...+75°C nom.
  • Page 54 JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc. Street address: JUMO House 8 Technology Boulevard Moritz-Juchheim-Straße 1 Temple Bank, Riverway Canastota, NY 13032, USA 36039 Fulda, Germany Harlow - Essex CM20 2DY, UK Phone: 315-697-JUMO...