Setting The Error Signal (S.err) - JUMO DELOS SI Operating Manual

Electronic pressure switch with display. b 40.5052.0
Hide thumbs Also See for DELOS SI:
Table of Contents

Advertisement

7 Commissioning
7.8.2 Setting the final value of scaling (Sc.Hi)
Setting
7.9

Setting the error signal (S.Err)

Setting
36
The output signal can only be scaled for instruments with
analog output!
Explanation See section 7.8.1 "Setting the starting value of scaling
(Sc.Lo)", page 35.
Setting range:
Factory setting:
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "Sc.Hi".
"Press"
Enter the value "digit by digit."
Only for instruments with analog output, an error signal is
generated for overrange or underrange!
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "S.Err".
"Press"
25 to 100% of the nominal measuring range
Final value of measuring range
"-" Flashing
Continuous