7 Commissioning
7.6

Setting the filter time constant (damping) (DamP)

7.7

Setting the output signal (S.TyP)

32
The filter time constant (damping) can be used to smooth the measured value.
Small filter time constant: the display is refreshed quickly.
Large filter time constant: Display refresh is slower.
The value is entered in seconds with two places after the decimal.
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "Dam.P".
"Press"
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
"Rotate" until the bottom line shows "S.TyP".
"Press"
Example
4.20A = output signal 4 ... 20 mA
0.20A = output signal 0 ... 20 mA
0.10U = output signal 0 ... 10 V