Setting Scaling - JUMO DELOS SI Operating Manual

Electronic pressure switch with display. b 40.5052.0
Hide thumbs Also See for DELOS SI:
Table of Contents

Advertisement

7.8

Setting scaling

Customer-
specific
measuring
range
Example
Scaling
Simple
example
Customer-
specific scaling
The customer measuring range (2) is defined by:
- Range start (4)
- Range end (5)
- Span (MSP)
Actual
The instrument has a nominal measuring range (1) from 0 to 4 bar
Target
The customer would like to measure the pressure in the range from 1 to 2 bar
(25% of the nominal measuring range).
Range start (5) is 1 bar
Range end (6) is 2 bar
Span (MSP) is 1 bar
0
The scaling of the instrument's output signal describes how the measured
pressure is converted into an output signal.
Actual
The instrument has a nominal measuring range (1) from 0 to 4 bar and
the instrument has an output signal from 4 to 20 mA (3).
Target
The customer would like:
the "Customer measuring range" (2) from 0 to 4 bar (100% of nominal
measuring range (1)
should correspond to the output signal (3) from 4 to 20 mA (100%).
The scaling is 1: 1 (100% to 100%).
0
4
It is often useful to scale part of the nominal measuring range to the
output signal.
1
2
4
5
1
2
100%
100%
7 Commissioning
3
4 bar
1
2
3
4 bar
1
2
3
20 mA
33