Validating the MODBUS protocol communication

You can use the following tests and methods to validate MODBUS protocol communication:
Computer-Gateway communication test
Computer-solar sensor communication test
Gateway-solar sensor communication test

Testing communication between computer and Gateway system

Procedure
1. Install the USB to RS485 adaptor driver.
A virtual serial port opens and displays the following message:
"Prolific USB-to-Serial Comm Port (COM5)."
For information on pin connector assignments, see DB9 connector pin assignments for RS485.
2. Route the cables:
a. Connect the Data+ to RX+ and RX+ to TX+ cable with a 120 ohm resistor in-between.
b. Connect the Data- to RX- and RX- to TX+ cable with a 120 ohm resistor in-between.
The serial port is configured with the following parameters:
Speed: 9600
Data bits: 8
Stop bits: 1
Validating the MODBUS protocol communication
31