Parity: None
•
Flow Control: None
3. Send a command string from the computer to the Gateway.
If the communication between the computer and the Gateway is established, the Gateway receives
the command string.
4. Send a command string from the Gateway to the computer.
If the communication between the Gateway and the computer is established, the computer receives
the command string.
NOTE:
While sending data, the receive pin on the Gateway also receives the sent data because TX and
RX cables are wired together. To fix this issue, disable the receive I/O of the Gateway when
sending data (requires software implementation).
Testing communication between computer and solar sensor
Procedure
1. Install the USB to RS485 adaptor:
•
Connect adaptor pin 1 to the solar sensor Data+/B pin.
•
Connect adaptor pin 1 to the solar sensor Data-/A pin.
For pin connector assignments, see RS485-solar sensor connector pin assignments.
2. Install the USB to RS485 adaptor driver.
3. Launch the Si Modbus Configurator application.
4. Reset the power supply:
a. Disconnect the power cable from the gateway.
b. Connect the power cable to the gateway.
Wait till the Sensor connected LED glows green.
32
Testing communication between computer and solar sensor