Environmental Type Tests - Siemens RUGGEDCOM RSG2488 Installation Manual

Hide thumbs Also See for RUGGEDCOM RSG2488:
Table of Contents

Advertisement

Test
IEC 61000-4-17
IEC 60255-5
IEC 1613/C37.90
IEC 1613/C37.90.1
IEC 1613/C37.90.2
IEC 1613/C37.90.3

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
IEC 60068-21-1
IEC 60068-21-2
Description
D.C. Power Ports
Ripple on D.C.
D.C. Power Ports
Power Supply
Dialiectric Strength
Signal Ports
D.C. Power Ports
A.C. Power Ports
H.V. Impulse
Signal Ports
D.C. Power Ports
A.C. Power Ports
Dialiectric Strength
Signal Ports
D.C. Power Ports
A.C. Power Ports
H.V. Impulse
Signal Ports
D.C. Power Ports
A.C. Power Ports
Oscillatory
Signal Ports
D.C. Power Ports
A.C. Power Ports
Fast Transient
Signal Ports
D.C. Power Ports
A.C. Power Ports
Earth Ground Ports
Radiated RFI
Enclosure Ports
ESD
Enclosure Contact
Enclosure Air
Description
Cold Temperature
Dry Heat
Vibration
Shock
Test Levels
10%
2 kVAC (Fail-
Safe Relay Output)
1.5 kVDC
2 kVAC
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV (Fail-Safe
Relay Output)
5 kV
5 kV
2 kVAC
1.5 kVDC
2 kVAC
2.5 kV common
mode @1 MHz
2.5 kV common, 1 kV
differential mode@1 MHz
+/- 4 kV @ 2.5 kHz
+/- 4 kV
35 V/m
+/- 8 kV
+/- 15 kV
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
2g @ 10 - 150 Hz
30 g @ 11 ms
Severity Levels
3
Test Levels