SOFTWARE SETUP
Creating a new
setpoint file
NOTE:
NOTE
NOTE:
NOTE
84
The EnerVista 3 Series Setup software allows the user to create new setpoint files
independent of a connected device. These can be uploaded to a relay at a later date. The
following procedure illustrates how to create new setpoint files.
1.
In the File pane, right click on File and select the New Settings File item. The following
box will appear, allowing for the configuration of the setpoint file for the correct
firmware version. It is important to define the correct firmware version to ensure that
setpoints not available in a particular version are not downloaded into the relay.
Discontinued order codes may be included to maintain back-compatibility of setpoint files.
For current order codes, refer to the GE Multilin website at
www.gegridsolutions.com/multilin.
Refer to the 3 Series Retrofit Instruction Manual for instructions on converting existing
Multilin MIF II or MIV II setpoint files.
2.
Select the Firmware Version, and Order Code options for the new setpoint file.
3.
For future reference, enter some useful information in the Description box to facilitate
the identification of the device and the purpose of the file.
4.
To select a file name and path for the new file, click the button beside the File Name
box.
5.
Select the file name and path to store the file, or select any displayed file name to
replace an existing file. All 350 setpoint files should have the extension 'SR3' (for
example, 'feeder1.SR3').
6.
Click OK to complete the process. Once this step is completed, the new file, with a
complete path, will be added to the EnerVista 3 Series Setup software environment.
CHAPTER 3: INTERFACES
http://
350 FEEDER PROTECTION SYSTEM – QUICKSTART GUIDE