QUICK SETUP SETTINGS

Quick Setup settings
100
The setpoints below can be programmed under the "Quick Setup" menu.
Note that monitoring of Breaker Status via 52a, 52b, or both of these contacts,, should be
programmed under
SETPOINTS > S2 SYSTEM SETUP > BREAKER
PATH:
QUICK SETUP >
PH CT PRIMARY
Range: 1 A to 6000 A in steps of 1
Default: 500 A
GND CT PRIMARY
Range: 1 A to 6000 A in steps of 1
Default: 50 A
VT CONNECTION
Range: Wye, Delta
Default: Wye
VT SEC VOLTAGE
Range: 50 V to 240 V in steps of 1
Default: 120 V
VT RATIO
Range: 1.0:1 to 5000.0:1 in steps of 0.1
Default: 1:1
AUX VT SECONDARY
Range: 50 V to 240 V in steps of 1
Default: 110 V
AUX VT RATIO
Range: 1.0:1 to 5000.0:1 in steps of 0.1
Default: 1:1
VT FUSE FAIL
Range: Trip, Disabled, Alarm
Default: Disabled
PH TOC FUNCTION
Range: Trip, Disabled, Latched Alarm, Alarm
Default: Trip
PH TOC PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
PH TOC CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse, Definite
Time, IEC Curve A/B/C and Short, IAC Extreme/Very/Inverse/Short, User
Curve, FlexCurve™ A/B (programmable curves)
Default: Extremely Inverse
PH TOC TDM
Range: 0.05 to 50.00
Default: 1.00
CHAPTER 4: QUICK SETUP - FRONT CONTROL PANEL
.
350 FEEDER PROTECTION SYSTEM – QUICKSTART GUIDE