CHAPTER 3: INTERFACES
350 FEEDER PROTECTION SYSTEM – QUICKSTART GUIDE
6.
The EnerVista 3 Series Setup software will notify the user when the 350 has finished
loading the file. Carefully read any displayed messages and click OK to return the
main screen. Cycling power to the relay is recommended after a firmware upgrade.
After successfully updating the 350 firmware, the relay will not be in service and will
require setpoint programming. To communicate with the relay, the communication
settings may have to be manually reprogrammed.
When communications is established, the saved setpoints must be reloaded back into the
relay. See Loading Setpoints from a File for details.
Modbus addresses assigned to firmware modules, features, settings, and corresponding
data items (i.e. default values, min/max values, data type, and item size) may change
slightly from version to version of firmware.
The addresses are rearranged when new features are added or existing features are
enhanced or modified.
SOFTWARE SETUP
89