CHAPTER 3: INTERFACES
Transient recorder
(Waveform capture)
350 FEEDER PROTECTION SYSTEM – QUICKSTART GUIDE
The user can save Configured Trip Times.
The user can export Configured Trip Times to a CSV file
The user can load Trip Times from a CSV File
The screen above shows the model followed by 350 for viewing Flexcurves. Select
Initialize to copy the trip times from the selected curve to the FlexCurve.
The EnerVista 3 Series Setup software can be used to capture waveforms (or view trace
memory) from the relay at the instance of a pickup, trip, alarm, or other condition.
With EnerVista 3 Series Setup software running and communications established,
select the Actual Values > A3 Records > Transient Records menu item to open the
Transient Recorder Viewer window.
Click on Trigger Waveform to trigger a waveform capture. Waveform file numbering
starts with the number zero in the 350 , so that the maximum trigger number will
always be one less than the total number of triggers available.
Click on the Save to File button to save the selected waveform to the local PC. A new
window will appear, requesting the file name and path. One file is saved as a
COMTRADE file, with the extension "CFG." The other file is a "DAT" file, required by the
COMTRADE file for proper display of waveforms.
To view a previously saved COMTRADE file, click the Open button and select the
corresponding COMTRADE file.