Inputs

NOTE:
NOTE
4–8
The MM200 digital (contact) inputs are programmed in this menu.
Inputs are automatically assigned based on typical wiring diagrams, shown in chapter 2,
when a pre-defined starter is selected.
The following setpoints are available for each contact input:
Function
Range: Access Switch, Comms Permissive, Contactor A Status, Contactor B Status, Field
Permissive, Field Start A, Field Start B, Field Stop, Forward Limit, Hard Wired Permissive,
Hard Wired Start A, Hard Wired Start B, Hard Wired Stop, Lockout Reset, MCC Permissive,
Remote Reset, Reverse Limit, Test Switch, Auto/Manual Switch, Power Failure Restart
Inhibit, Power Failure Input.
Default: None
"Access Switch": This value represents an open contact that disables security
access of selected levels. When closed, sets the access level to the value
configured in Security > Access Switch Level.
"Auto/Manual": "Close" sets the auto mode. "Open" sets the manual mode.
"Comms Permissive": This value represents an open contact that disables
communications control. Used by the auto/manual control element.
"Contactor A Status": This value represents the normally open auxiliary contact of
contactor A. Used by the starters, the stop/start control element, and the system
trouble function. Automatically assigned to the first input when a starter type is
selected. Not otherwise user-programmable.
"Contactor B Status": This value represents the normally open auxiliary contact of
contactor B. Used by the starters, the stop/start control element, and the system
trouble function. Automatically assigned to the second input when a reversing or
two-speed starter type is selected. Not otherwise user assignable.
"Field Permissive": This value represents an open contact which disables field
control. Used by the auto/manual control element.
"Field Start A": This value represents a field-located manual switch requesting
contactor A pickup. Used by the auto/manual control element.
"Field Start B": This value represents a field-located manual switch requesting
contactor B pickup. Used by the auto/manual control element.
"Field Stop": This value represents a field-located manual switch where an open
position requests stop. Used by the auto/manual control element.
"Forward Limit": This value represents a contact which opens at the forward travel
limit. Used by the reversing starter type.
"Hard Wired Permissive": This value represents an open contact that disables
hard-wired control. Used by the auto/manual control element.
"Hard Wired Start A": This value represents an auto contact (typically from a PLC)
requesting contactor A pickup. Used by the auto/manual control element.
"Hard Wired Start B": This value represents an auto contact (typically from a PLC)
requesting contactor B pickup. Used by the auto/manual control element.
"Hard Wired Stop": This value represents an auto contact (typically from a PLC)
where the open position requests stop. Used by the auto/manual control
element.
"Lockout Reset": This value represents a contact input used to reset lockouts, trips,
and alarms.
"NA": This value indicates the contact Input has no assigned function.