MM200 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
Motor FLA (Mandatory setpoint)
Range: 0.5 to 1000.0 amps in steps of 0.1
Default: OFF
This setpoint must be specified for motor protection. The value may be taken from the
motor nameplate data sheets.
Supply Frequency (Mandatory setpoint)
Range: 50 Hz, 60 Hz
Default: 60 Hz
This setpoint specifies the nominal system frequency.
The following sections provide additional information for each starter type.
Figure 4-1: Typical starter timing
P
T
P
P
CONFIGURATION SETPOINTS
T
T
888754A1.CDR
P - Pre-contactor Time setting
T - Transfer Time setting
R - Ramp Down Time setting
4–3