Emc Standards - Danfoss FCM305 56 Instruction Manual

Vlt drivemotor fcm 300 series
Table of Contents

Advertisement

EMC Standards

NOTE!
-
All EMC specifications are stated with
factory settings.
-
Maximum 4 kHz switching frequency.
-
Shielded data/control cables must be
used for surge protection.
-
The FCM 300 must be connected to
ground in order to comply.
-
Maximum/minimum line impedance
Z
= 0.24 + j0.15 ohm; Z
max
j0 ohm.
(EN 61800-3 commutation notches)
Generic standards
The generic standards are stated in the EMC
directive (89/336/EEC).
The FCM 300 complies with:
1)
EN 50081-1
, EN 50082-1.
Residential, commercial and light industrial
environment.
EN 50081-2, EN 50082-2.
Industrial environment.
1)
Emission levels stated by EN 50081-1 are only
fulfilled by FCM 300 with class B-1 optional filter.
Furthermore the FCM 300 complies with:
2)
DIN VDE 0160/1990
2)
'Protection against overvoltage 7.3.1. class1'
Product standards
The product standards are stated in EN 61800-3
(IEC 1800-3).
The FCM 300 complies with:
EN 61800-3, unrestricted distribution
EN 61800-3, restricted distribution.
3)
Emission levels stated by EN 61800-3 unrestricted
distribution are only fulfilled by FCM 300 with class
B-1 filter.
Basic standards, emissions
-
EN 55011: Limits and methods of measuring
radio disturbance characteristics of industrial,
scientific and medical (ISM) radio-frequency
equipment.
MG.03.B6.2G - VLT is a registered Danfoss trademark
= 0 +
min
3)
.
FCM 300 Series
-
EN 55022: Limits and methods of measuring
radio disturbance characteristics of information
technology equipment.
-
EN 61000-3-2: Limits for harmonic current
emissions (equipment input current ≤16 A)
-
EN 61000-3-4: Limits for harmonic current
emissions (equipment input current ≥16 A)
Basic standards, immunity
-
EN 61000-2-4 (IEC 1000-2-4):
Compatibility levels
Simulation of voltage and frequency
fluctuations, harmonics and commutation
notches on the power line.
-
EN 61000-4-2 (IEC 1000-4-2):
Electrostatic discharge (ESD)
Simulation of electrostatic discharge.
-
EN 61000-4-4 (IEC 1000-4-4):
Fast transients, burst 5/ 50 nS
Simulation of transients caused by switching of
contactors, relays or similar devices.
-
EN 61000-4-5 (IEC 1000-4-5):
Surges 1.2/ 50 µS.
Simulation of transients caused by e.g. lightning
that strikes near an installation.
-
EN 61000-4-6: (IEC 1000-4-6):
Radio-frequency electromagnetic field.
Amplitude modulated.
Simulation of interference caused by radio
transmission equipment.
-
ENV 50140:
Radio-frequency electromagnetic field. Pulse
modulated.
Simulation of interference caused by GSM
mobile phones.
General aspects of EMC emissions
For high frequency shielding, shielded cables used
for Profibus, standard bus, control cables and signal
interface must in general be connected to the
enclosure at both ends.
General aspects of EMC immunity
If there are problems with low frequency
interference (ground loops), shielded cable used for
Profibus, standard bus, control cables and signal
interface can be left open at one end.
17-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents