Warning words 1 + 2 and Alarm word
Warning words 1 + 2 and alarm word are shown on
the display in Hex format. If there are more than one
warning or alarm, a sum of all warnings or alarms
will be shown.
Warning words 1 + 2 and alarm word can also be
displayed using the serial bus in parameter 540, 541
and 538.
Bit (Hex)
Warning word 1
00000008
HPFB timeout
00000010
Standard bus timeout
00000040
Current limit
00000200
Inverter overload
00001000
Voltage warning low
00002000
Voltage warning high
00004000
Phase loss
00010000
Live zero error warning
00400000
Output freq. limit warning
00800000
HPFB error
40000000
24 V supply warning
80000000
Inverter temp. high
Bit (Hex)
Warning word 2
01
Ramping
04
Start clockwise/
counterclockwise
08
Slow down
10
Catch-up
8000
Frequency limit
Bit (Hex)
Alarm word
00000002
Trip lock
00000040
HPFB timeout
00000080
Standard bus timeout
00000100
Short circuit
00000200
24 V supply fault
00000400
Earth ground fault
00000800
Overcurrent
00004000
Motor thermistor
00008000
Inverter overload
00010000
Undervoltage
00020000
Overvoltage
00040000
Phase loss
00080000
Live zero error
00100000
Overtemperature
02000000
HPFB error
08000000
Inrush fault
10000000
Internal error
MG.03.B6.2G - VLT is a registered Danfoss trademark
FCM 300 Series
16-5