200 Rotation direction (ROTATION)
Settings:
Only clockwise,
0-132 Hz (132 Hz CLOCK WISE)
Both directions,
0-132 Hz (132 Hz BOTH DIRECTIONS)
Only counterclockwise, 0-132 Hz
(132Hz COUNTERCLOCKW.)
Function:
This parameter guarantees protection against
unwanted reversing.
Using Process, closed loop mode (parameter 100)
parameter 200 must not be changed to Both
directions [1].
Description of choice:
Select the desired direction seen from the motor
drive end.
Note that if Only clockwise, 0-132 Hz [0]/Only
counterclockwise, 0-132 Hz [2] is selected, the
output frequency will be limited to the range f
f
.
MAX
If Both directions, 0-132 Hz [1] is selected, the
output frequency will be limited to the range ± f
(the minimum frequency is of no significance).
NOTE!
This is only possible in Stop Mode (motor stopped on
a Stop command).
201 Min. output frequency
(MIN OUTPUT FREQ)
Settings:
0.0 H
- f
(parameter 202)
Z
MAX
0.0 H
Z
6.0 Hz
H
Function:
In this parameter, a minimum motor frequency limit
can be selected that corresponds to the minimum
frequency at which the motor is to run.
= General factory setting - also applying to spare part unit, H H H H H = HVAC setting, I I I I I = Industrial setting, ( ) = parameter
window text. [ ] = value for use in communication via serial communication port
10-2
FCM 300 Series
The minimum frequency can never be higher than
the maximum frequency, f
[0]
If Both directions has been selected in parameter
200, the minimum frequency is of no significance.
[1]
Description of choice:
[2]
A value from 0.0 Hz to the max. frequency selected
in parameter 202 (f
202 Max. output frequency
(MAX OUTPUT FREQ)
Settings:
f
(parameter 201) - f
MIN
f
RANGE
Function:
In this parameter, a maximum motor frequency can
be selected that corresponds to the highest
frequency at which the motor is to run.
See also parameter 205.
-
MIN
Description of choice:
A value from f
MAX
203 Reference/feedback range
(REF/FEEDB. RANGE)
Settings:
Min - Max (MIN - MAX)
- Max - + Max (-MAX-+MAX)
Function:
This parameter decides whether the reference
signal is to be positive or can be both positive and
negative.
[0 - ]
[0]
NOTE!
[60]
Analogue input (reference/feedback) can only be
positive.
Choose Min - Max [0] if Process, closed loop mode
has been selected in parameter 100.
MG.03.B6.2G - VLT is a registered Danfoss trademark
.
MAX
) can be chosen.
MAX
(132 Hz, par. 200)
RANGE
to 132 Hz can be selected.
MIN
[0]
[1]