How to Read the Parameter Settings
Before working with the parameter settings, it is
important to note that there are various settings
depending on the product.
The standard parameter settings (general factory
.
settings) are marked with
listed in the back of this manual under "Standard
Parameter Settings".
However, there are some special settings only
applicable for HVAC and industrial products.
Whereever these settings are applied, it is marked
with "H H H H H " for HVAC products and "I I I I I " for industrial
products.
The settings differing from the standard parameter
settings are also listed in the back of the manual.
NOTE! If H or I is not stated, the standard
parameters settings are to be used.
001 Language
(LANGUAGE)
Settings:
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
State when delivered may vary from factory setting.
Function:
The choice in this parameter defines the language
to be used on the display.
Description of choice:
There is a choice of English [0], German [1], French
[2], Danish [3], Spanish [4] and Italian [5].
= General factory setting - also applying to spare part unit, H H H H H = HVAC setting, I I I I I = Industrial setting,
( ) = display text [ ] = value for use in communication via serial communication port
8-2
. These settings are
[0]
[1]
[2]
[3]
[4]
[5]
FCM 300 Series
002 Local/remote control
(OPERATION SITE)
Settings:
Remote control (REMOTE)
Local control (LOCAL)
Function:
There is a choice of two methods of controlling the
FCM 300: Remote control [0] and Local control [1].
Description of choice:
If Remote control [0] is selected, the FCM 300 can
be controlled via:
1. The control terminals or the serial communication
port .
2. The [START] key. However, this cannot override
Stop commands (also start-disable) entered via
the digital inputs or the serial communication
port.
3. The [STOP], [JOG] and [RESET] keys, provided
that these are active (see parameters 014, 015
and 017).
If Local control [1] is selected, the FCM 300 can be
controlled via:
1. The [START] key. However, this cannot override
Stop commands on the digital terminals (if [2] or
[4] has been selected in parameter 013).
2. The [STOP], [JOG] and [RESET] keys, provided
that these are active (see parameters 014, 015
and 017).
3. The [FWD/REV] key, provided that this has been
activated in parameter 016 and that in
parameter 013 a choice of [1] or [3] has been
made.
4. Via parameter 003 the local reference can be
controlled by means of the " [ ]" and " [ ]" keys.