3.4.12 Recommended wire sizes

All wire sizes are based on 75 °C (167 °F) copper wire. Use copper conductors only. Higher
temperature smaller gauge wire may be used per National Electric Code (NEC) and local codes.
MotiFlex e100
catalog number
catalog number
3-22 Basic Installation
MFE..A001
MFE..A003
MFE..A006
MFE..A010
MFE..A016
MFE..A021
MFE..A026
MFE..A033
MFE..A048
MFE..A065
Table 3 - AC input and motor output wire sizes
AC input & motor output wire size
AWG
14
14
14
10
10
8
8
8
4
4
www.baldormotion.com
2
mm
2.5
2.5
2.5
6.0
6.0
10.0
10.0
10.0
20.0
20.0