3.4.1 Single-phase connection to package sizes A, B, C, D

Location Connector X1
Part number MDH1A...
Nominal input
* The required 230VAC supply may also be derived from two phases of a U.S. 230VAC
3-phase supply, i.e. 230VAC line to line. Connect one phase to L and the other phase to N.
For single-phase connection, the voltage ripple on the DC-bus is 25Vp-p for 5A peak current
rising to 50Vp-p for 10A peak current. This can limit the maximum speed of the motor.
Tightening torque for terminal block connections is 0.5-0.6Nm (4.4-5.3 lb-in).
The threaded hole in the top of the enclosure is for protective earth/ground connections.
The threaded hole in the bottom of the enclosure may be used as an additional functional
earth/ground connection for signals on connector X3. It may also be used to attach strain relief
clamps. The holes are threaded for M4 bolts no longer than 12mm (0.47 in) in length. Longer
bolts may short circuit the electrical components inside the MintDrive
AC
Supply
Line (L)
Neutral (N)
Note: For CE compliance, a filter must be connected between the AC power supply and
MN1901
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
(Mating connector: Phoenix COMBICON MVSTBW 2,5/9-ST, 5mm pitch)
115VAC, 1Φ line to neutral
voltage
(U.S. single phase supply)
Range 75-125VAC
Route L, N, and
Circuit breaker or fuse.
earth/ground together
See section 3.4.4
in conduit or cable
Isolating switch
Incoming safety
earth/ground (PE)
STAR POINT
Figure 2 - Earthing/grounding for single-phase installations
II
the MintDrive
. If local codes do not specify different regulations, use at least the
same gauge wire for earth/ground as is used for L and N.
MDH2A...
230VAC, 1Φ line to neutral
(European single phase supply)*
75-250VAC
AC filter.
See section
3.4.5
*
* If filter has no
If AC power wires
output
are shielded,
earth/ground
earth/ground
terminal, earth
outer shield using
wire may be
360º clamps
connected directly
connected to
to star point.
backplane.