Honeywell GSMV4G Installation And Setup Manual page 31

Intellipath series 4g gsm communicator
Table of Contents

Advertisement

PROMPTS
Pwr Loss Rpt Y/N
22
(Y)_
Low Bat Rpt Y/N
23
(Y)_
Tamper Rpt Y/N
24
(Y)_
Lynx Panic Y/N
25
(N)_
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the
communicator's zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the communicator's zone
terminals and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2
serving as a reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell
output to the communicator zone causes a bell fault on the control panel, enable the "Trip Inputs 1 or 2" option. The
communicator reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary)
when it detects a steady signal.
UL: Use of the Bell output is not supported.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the Telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a Telco line fault or open/close report respectively,
in ADEMCO High-Speed format. Connect the appropriate trigger from the control panel to the selected zone input
for each of these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the
following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
4204/
ZONE
OPTIONS
2-4204
TRIG.
[Y], [N]
X
X
[Y], [N]
X
X
[Y], [N]
X
X
[Y], [N]
X
Important Information Regarding Zone Input Options
Section 3: Programming the Communicator
DESCRIPTION
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after power is
restored.
UL/ULC Standard Installations (using
transformer and battery): Must be set to "Y" unless
used with a LynxR-I series control. Must be set to
"N" when using a LynxR-I series control.
ULC Commercial Fire & Burglary Installations
(powered from the control panel): Must be set to "N."
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery condition
clears.
Alternate Installations (powered from the control
panel): Must be set to "N."
UL/ULC Standard Installations (using
transformer and battery): Must be set to "Y" unless
used with a LynxR-I series control. Must be set to
"N" when using a LynxR-I series control.
ULC Commercial Fire & Burglary Installations
(powered from the control panel): Must be set to "N."
Sends a tamper report when the communicator
detects a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
UL/ULC: Must be set to "Y."
Applies only if used with a Lynx, LynxR or
LynxR-EN controls where the communicator (or
LRR) trigger is connected to the communicator's
zone terminal.
Reports a Panic alarm on zone 3 when the
communicator detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
3-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gsmvcn4g

Table of Contents