Alternative Mode Programming (Zone Trigger, 4204 and Two-4204)

UL / ULC

Zone Trigger Mode

There are six input zones available on the communicator. Each zone is selectable for +V, -V,
or EOLR trigger. The first zone input can detect both pulsed and steady signals if connected
to a bell output.
When using Zone Trigger mode, messages are sent in ADEMCO High-Speed format.
Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10.
Refer to Table 3-4 for Zone Trigger Mode programming and follow the prompts that pertain
to Zone Trigger Mode.

4204 Emulation Mode

In 4204 Emulation Mode, the GSMV4G communicates with a compatible Honeywell VISTA
series or First Alert control panel as though it were a 4204 Relay Module. If two 4204s are
enabled in the communicator, it acts as two 4204s at consecutive device addresses. The
control panel must be configured to recognize one or two 4204 relay modules accordingly. On
VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13
should not be used when the secondary 4204 is enabled. Messages are sent in ADEMCO
High-Speed format.
NOTE: See your control panel Installation and Setup Guide for the number of 4204 modules

4204 Emulation Mode Options

For control panels that do not support ECP communication, the 4204 Emulation modes
provide a means of sending up to eight unique reports based on defined system conditions.
In 4204 mode, the communicator functions as a logical 4204 Relay Module, where each relay
number, referred to in the communicator as zone number, can be programmed to send a
report based on the output function programmed in the control panel for that relay. Each
relay-zone can be programmed to; send a restore message of the reported condition, delay the
transmission of messages, and to send reports only when a conditional zone is triggered
(armed). See "Important Information Regarding Zone Input Options" later in this section.
In single 4204 mode, the communicator supports up to four relay-zones. In Two-4204 mode,
the communicator functions as two 4204 modules, supporting up to eight relay-zones.
UL
3-8
Communicator shutdown.
Communicator power on / reset AND the control panel lost communications with
the communicator.
Communicator power on / reset AND tamper detected.
Communicator power on / reset AND tamper detected AND not registered.
Communicator tamper detected AND communicator battery low.
Primary power loss (will only be displayed in conjunction with another event).
Battery charger failure (will only be displayed in conjunction with another event).
Low battery (will only be displayed in conjunction with another event).
The LYNX controls have not been evaluated with this communicator.
supported.
4204 Mode and Two-4204 Mode has not been evaluated.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gsmvcn4g

Table of Contents