GSMV4G/GSMVCN4G Installation and Setup Guide
PROMPTS
Old Alarm Time
24
10 Minutes_
GSM Flt Time
25
(00 mins)_
Flt Rel ON Y/N
26
(N)_
Pwr Loss Rpt Y/N
27
(Y)_
Low Bat Rpt Y/N
28
(Y)_
Tamper Rpt Y/N
29
(Y)_
ECP mode supports two optional hardwire zone input triggers by making connections to the communicator's zone 6
and/or zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
UL: Set V+ to inverted, and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed
format.
3-6
OPTIONS
•10 Minutes
The old alarm time sets how long an undeliverable alarm is retried
• 4 Hours
for delivery to the central station. If the message is not validated, it
• 15 Minutes
is retried until the old alarm time is reached or the message is
• 8 Hours
validated.
• 30 Minutes
Press the [space] key to scroll through choices.
• 12 Hours
• 1 Hour
• 24 Hours
UL/ULC: Must be set to 10 minutes.
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
In the event the communicator detects a communication path
[00-99]
failure, enter the time delay (in minutes) before the communicator
[00] = not used
notifies the control panel with a trouble message (and trips the
Fault Output if used; (terminal 11) see next prompt). The control
panel can then notify the central station.
UL/ULC: Must be one (01) minute.
If enabled, the fault open collector output is normally energized to
[Y], [N]
ground, and de-energizes (open circuit) in the event of a
communicator fault. For conditions that trip the fault relay refer to
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring the Fault Relay in Section 2.
UL/ULC: Must be set to "Y."
Sends a primary power loss report to the central station within 1-3
[Y], [N]
hours after its detection. A restore report is sent within 1-3 hours
after power is restored.
UL/ULC: Must be set to "Y."
Sends a low-battery report when a low battery condition exists.
[Y], [N]
UL/ULC: Must be set to "Y."
[Y], [N]
Sends a tamper report when the communicator detects a tamper
condition. A tamper restore is automatically sent when the tamper
condition clears.
UL/ULC: Must be set to "Y."
Important Information Regarding Zone Input Options