See the following illustration for the routing of the frame ground strap from the floor pedestal,
through the floor, to the frame of the rack.
1 Screw on Ground Clamp (for tightening the
clamp)
2 Grounding Clamp
3 Metal Floor Pedestal
4 Bottom Left Side of the Rear of the Rack
b. Position the ground strap clamp (part number 5457808) around a grounded floor pedestal.
c. Using a screwdriver, tighten the ground strap clamp screw to secure the clamp to the floor
pedestal.
d. Attach the other end of the ground strap to the ground strap clamp on the floor pedestal.
4. To install a frame ground strap at the bottom right side of the rear of the rack, do the following:
a. At the bottom right side of the rear of the rack, attach the lug end of the ground strap (part number
44P2814) to the ground connection symbol on the rack using a screw (part number 2665528) and
a lockwasher (part number 1623347, if supplied). Tighten the screw using an 8-mm nutdriver.
Note: If a starwasher is supplied, ensure that the starwasher is installed between the frame
surface and the ground strap lug.
See the following illustration for the routing of the frame ground strap from the floor pedestal,
through the floor, to the frame of the rack.
122
Eserver pSeries 670 Installation Guide
4
3
2
1
Left Rear of Rack
5
6
7
8
5 Starwasher (install if supplied)
6 Lug on Ground Strap
7 Screw (for attaching lug to the rack)
8 Ground Strap