Code list
35*
Blocking position
[0] mm/° /%
ESC
Reset
36*
[OFF]
RUN
ESC
37
Position transmitter
Yes No
38*
Inductive alarm
[NO]
YES
ESC
39
System deviation e info
–99.9 to 999.9 % ,
40
Transit time Open info
0 to 240 s [0]
41
Transit time Closed info
0 to 240 s [0]
Auto-w info
42
0.0 to 100.0 % of the span
4 to 20 mA
43
Firmware info
Xxxx
44
y info
[0] OP
0 to 100 %
MAX
78
EB 8384-2 EN
Entering the blocking position.
Distance up to CLOSED position.
Only necessary in initialization mode SUb.
Resets all start-up parameters to default (factory setting).
Note: After setting RUN, the positioner must be re-initialized.
Display only,
indicates whether the position transmitter option is installed.
Indicates whether the inductive limit switch option is installed or
not.
Display only,
indicates the deviation from the set point position (e = w–x).
Display only,
minimum opening time is determined during initialization
Display only,
minimum closing time is determined during initialization
Display only,
indicates the supplied automatic reference variable corre-
sponding 4 to 20 mA.
Display only,
indicates the current firmware version of the positioner.
Display only.
The control signal y is indicated in %, based on the travel range
determined on initialization.
MAX: The positioner builds up its maximum output pressure. See
description for Code 14, 15.
0: The positioner vents completely. See description for Code 14,
15.
– – –: The positioner has not been initialized.