5
Mounting / Installation
Detector base seal RS720
5.3 Detector base seal RS720
36
Building Technologies
Fire Safety
Use the detector base seal RS720 to install point detectors in wet rooms.
l
Protection category: IP42.
Compatible with the following detector bases:
l
–
Detector base (collective) DB110
–
Detector base (collective) DB110R
–
Detector base (collective) DB110D
–
Detector base (collective) DB110RD
Only use for recess-mounted cable entry.
l
Installation
1. NOTICE! Excessively large holes in the detector base seal will impair the
potential IP protection category. Do not cut or drill holes in the detector base
seal. Without using a tool, push the lines through the detector base seal.
2. Fit the detector base seal RS720 between the ceiling and the detector base.
Installing the detector base seal RS720
A6V10316298_e_en_--
2014-05-21