5.2 Detector base (collective)
Building Technologies
Fire Safety
DB110 / DB110x / DB110xx
Install the detector base directly on the ceiling.
l
Insert the cables into the detector base. You have the option of using the
l
following types of line:
Recess-mounted cable entry
Surface-mounted cable entry (cable diameter max. 8 mm)
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
The cable loops must be placed flat in the base bottom.
The bare length of the cables is approximately 8...10 mm.
1
2
1
Minimum Ø 40 mm
Use the detector bases DB110D and DB110RD if you are installing a fire
detection system in accordance with BS 5839, part 1.

Detector base (collective) DB110 / DB110x / DB110xx

2
Maximum Ø 90 mm
Mounting / Installation
A6V10316298_e_en_--
2014-05-21
5
35