Siemens OH110 Technical Manual page 55

Automatic fire
Table of Contents

Advertisement

Ambient conditions
Mechanical data
Standards
Building Technologies
Fire Safety
Operating temperature/permissible
ambient temperature:
HI110
l
HI112 with 'A2S' parameter set
l
HI112 with 'B' parameter set
l
Storage temperature
Air humidity
Protection categories according to
EN 60529 / IEC 60529:
Bases DB110, DB110x, DB110xx
l
(all installation types)
Bases DB110, DB110x, DB110xx with
l
detector base seal RS720
Bases DB110, DB110x, DB110xx with
l
base attachment wet BA721
Electromagnetic compatibility:
10 kHz...1.8 GHz
l
1.8 GHz...2.5 GHz
l
Color
European standards
Technical data for heat detectors HI110 / HI112
-10...+50 °C
-10...+50 °C
-10...+65 °C
-30...+70 °C
≤95 % rel.
IP40
IP42
IP44
50 V/m
20 V/m
∼RAL 9010 pure white
EN 54-5
Specifications
8
55
A6V10316298_e_en_--
2014-05-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Op110Hi110Hi112