Specifications - Siemens OH110 Technical Manual

Automatic fire
Table of Contents

Advertisement

4
Planning
Multi-sensor fire detector
4.2.2
Name
Thermal
Typ. response
time
[s]
Sensitive
10
Robust
35
3
30
Building Technologies
Fire Safety

Specifications

The table below shows the properties of the parameter sets for the multi-sensor fire
detector OH110:
Sensitivity
Static activation
temperature
[%/m]
[°C]
2,5
60
3,5
60
Applicable with fast temperature increases >10 K/min.
1
Between 1 K/min and 10 K/min, this value increases by a few degrees.
2
The response time is reduced in the first three minutes following the detector
3
line being started up or reset. The reduced response time enables the point
detector to be tested with test gas.
All parameter sets meet the criteria of standard EN 54-7.
Differential activation
Differential activation
temperature
possible from:
1
∆T [K]
[°C]
25
10
2
25
10
2
A6V10316298_e_en_--
2014-05-21