Siemens OH110 Technical Manual page 53

Automatic fire
Table of Contents

Advertisement

Device characteristics
Connections
Ambient conditions
Mechanical data
Standards
Building Technologies
Fire Safety
Response sensitivity
at 0.2 m/s (typ.)
Permissible wind speed
Compensation speed
Flashing interval times AI:
Detector line and external alarm
indicators:
Design
l
Cable cross section
l
Operating temperature/permissible
ambient temperature
Storage temperature
Air humidity
Protection categories according to
EN 60529 / IEC 60529:
Bases DB110, DB110x, DB110xx
l
(all installation types)
Bases DB110, DB110x, DB110xx with
l
detector base seal RS720
Bases DB110, DB110x, DB110xx with
l
base attachment wet BA721
Electromagnetic compatibility:
10 kHz...1.8 GHz
l
1.8 GHz...2.5 GHz
l
Color
European standards
Technical data for smoke detector OP110
1.8 or 2.5 %/m (depending on the parameter
set)
Max. 5 m/s
≤1/45 voltage increase for detection/h
See chapter 'Internal alarm indicator'
Screw terminal
2 x 0.2...1.6 mm
2
-10...+50 °C
-30...+70 °C
≤95 % rel.
IP40
IP42
IP44
50 V/m
20 V/m
∼RAL 9010 pure white
EN 54-7
Specifications
8
53
A6V10316298_e_en_--
2014-05-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Op110Hi110Hi112

Table of Contents