5.8 Cable entry
5.8.1
Building Technologies
Fire Safety
The detector bases DB110, DB110x and DB110xx feature four screw terminals. A
maximum of 2 cables may be connected to each screw terminal.
The cable cross section of the screw terminals is 0.2...1.6 mm
Terminal name
1a
1b
5
6
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8...10 mm.
Auxiliary terminals DBZ1190-AA/-AB
Use the following auxiliary terminals for multiple connections:
DBZ1190-AB connection terminal 1...2.5 mm²
l
DBZ1190-AA micro terminal 0.28...0.5 mm²
l
Detector base with connection terminals and micro terminals
Mounting / Installation
Connection
+Connection for external alarm indicator
+Collective detector line IN and OUT
-Collective detector line IN (from the control panel) / -
external alarm indicator
-Collective detector line OUT (from the EOL) / -external alarm
indicator
5
Cable entry
.
2
43
A6V10316298_e_en_--