Technical Data For Smoke Detector Op110 - Siemens OH110 Technical Manual

Automatic fire
Table of Contents

Advertisement

8
Specifications

Technical data for smoke detector OP110

Ambient conditions
Mechanical data
Standards
8.2 Technical data for smoke detector OP110
Detector line
External alarm indicators
52
Building Technologies
Fire Safety
Operating temperature/permissible
ambient temperature
Storage temperature
Air humidity
Protection categories according to
EN 60529 / IEC 60529:
Bases DB110, DB110x, DB110xx
l
(all installation types)
Bases DB110, DB110x, DB110xx
l
with detector base seal RS720
Bases DB110, DB110x, DB110xx
l
with base attachment wet BA721
Electromagnetic compatibility:
10 kHz...1.8 GHz
l
1.8 GHz...2.5 GHz
l
Color
European standards
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document A6V10301051
l
Operating voltage
Maximum current connection factor
Quiescent current at maximum current
connection factor
Surge current at maximum current
connection factor
Alarm voltage at:
Alarm current = 1...15 mA
l
Alarm current = 35 mA
l
Alarm current = 50 mA
l
Alarm current at operating voltage
UB = DC 5...28 V
Reset voltage UR:
Alarm is reliably reset
l
Alarm may possibly not be reset
l
Protocol
Compatibility
Number of external alarm indicators that
can be connected
Voltage
Current
-10...+50 °C
-30...+70 °C
≤95 % rel.
IP40
IP42
IP44
50 V/m
20 V/m
∼RAL 9010 pure white
CEA 4021
l
EN 54-7
l
DC 16...28 V
1
Max. 100 μA
160 μA
DC 5...10 V
DC 18...22 V
DC 26...28 V
4...50 mA
DC 0...2 V
DC 2...4 V
Collective (with and without current limitation)
See 'List of compatibility'
Max. 2
DC 9...30 V
10...16 mA
A6V10316298_e_en_--
2014-05-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Op110Hi110Hi112

Table of Contents