Preparing The Installation Site; Cabling Infrastructure; Installation Location - Brocade Communications Systems NetIron CES 2000 Series Hardware Manual

Hide thumbs Also See for NetIron CES 2000 Series:
Table of Contents

Advertisement

Foundry Hardware Installation Guide for the NetIron CES 2000 Series
WARNING: Disconnect the power cord from all power sources to completely remove power from the device.
WARNING: Make sure to choose the appropriate circuit device depending on the number of AC power supplies
installed in the chassis. The minimum current draw for the system is one AC power supply.
WARNING: Power supplies are hot swappable. However, Brocade recommends that you disconnect the power
supply from AC power before installing or removing the supply. The device can be running while a power supply is
being installed or removed, but the power supply itself should not be connected to a power source. Otherwise, you
could be injured or the power supply or other parts of the device could be damaged.
WARNING: Make sure that the power source circuits are properly grounded, then use the power cord supplied
with the device to connect it to the power source.
WARNING: If the installation requires a different power cord than the one supplied with the device, make sure
you use a power cord displaying the mark of the safety agency that defines the regulations for power cords in your
country. The mark is your assurance that the power cord can be used safely with the device.
CAUTION:
All devices with DC power supplies are intended for installation in restricted access areas only. A
restricted access area is where access can be gained only by service personnel through the use of a special tool,
lock and key, or other means of security, and is controlled by the authority responsible for the location.
CAUTION:
For the DC input circuit (DC power supply part number RPS9-DC), make sure there is a Listed 20
amp circuit breaker, minimum 48Vdc, double pole, on the input to the power supply. The input wiring for connec-
tion to the product should be Listed copper wire, 12 AWG, marked VW-1, and rated minimum 90 C.
CAUTION:
For a DC system (DC power supply part number RPS9-DC), use a grounding wire of at least 6
American Wire Gauge (AWG). The 6 AWG wire should be attached to an agency-approved crimp connector,
crimped with the proper tool.

Preparing the Installation Site

Cabling Infrastructure

Ensure that the proper cabling is installed in the site. See "Hardware Specifications" on page C-1 or
www.foundrynetworks.com for a summary of supported cabling types and their specifications.
WARNING: The intra-building port(s) of the equipment or subassembly is suitable for connection to intra-building
or unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly MUST NOT be
metallically connected to interfaces that connect to the OSP or its wiring. These interfaces are designed for use as
intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require isola-
tion from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order to con-
nect these interfaces metallically to OSP wiring.

Installation Location

Before installing the device, plan its location and orientation relative to other devices and equipment. Allow at least
3" of space at the front of the device for the twisted-pair, fiber-optic, and power cabling. Also, allow a minimum of
3" of space between the sides and the back of the device and walls or other obstructions.
The NetIron CES 2000 is suitable for installation in Network Telecommunications facilities and locations where the
NEC (National Electric Code) apply.
3 - 4
© 2009 Brocade Communications Systems, Inc.
March 2009