Installing The Device; Desktop Installation; Rack Mount Installation - Brocade Communications Systems NetIron CES 2000 Series Hardware Manual

Hide thumbs Also See for NetIron CES 2000 Series:
Table of Contents

Advertisement

Foundry Hardware Installation Guide for the NetIron CES 2000 Series
Figure 3.3 Inserting the NetIron CES 2000 DC Wiring Assembly
Chassis Attachment
Screws
8.
Connect the wire to your DC power source, making sure to connect the -48V cable to the negative terminal on
the power supply and the 0V cable to the positive terminal as marked on the power supply.
The equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
WARNING: DC return shall be isolated from the chassis ground (DC-I) when connections to the power supply
are made.
CAUTION:
For the NEBS compliant installation of a NetIron CES 2000 Series devices with AC and DC system
use a ground wire of at least 8 American Wire Gauge (AWG). The ground wire should have an agency-approved
crimped connector (provided with the chassis) attached to one end, with the other end attached to building
ground. The connector must be crimped with the proper tool, allowing it to be connected to both ground screws on
the enclosure. Before crimping the ground wire into the provided ground lug, insure the bare copper wire has been
cleaned and antioxidant is applied to the bare wire.
CAUTION:
To insure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug."

Installing the Device

You can install Foundry systems on a desktop, or in an equipment rack.

Desktop Installation

1.
Set the device on a flat desktop, table, or shelf. Make sure that adequate ventilation is provided for the system
– a 3-inch clearance is recommended on each side.
2.
Go to "Powering On the System" on page 3-13.

Rack Mount Installation

For rack mount installation, Foundry recommends that you use the rack mount ears attached to the unit . Each unit
ships with rack ears attached to the front of the unit. You can mount the rack ears in 4 different locations on the
device.
3 - 8
Assembly Screws
© 2009 Brocade Communications Systems, Inc.
March 2009