required to be applied to the mounting hardware used to attach the ground lug."
Installing an DC Power Supply
WARNING: Before beginning the installation, see the precautions in "Power Precautions" on page 3-3.
Use the following procedures for DC power supplies in NetIron CES and CER 2000 Series devices.
To install an DC power supply, do the following:
1.
If necessary, remove the power supply locking screws located in the upper left and the bottom right of the
device.
2.
If the empty power supply bay has a cover plate, remove the two screws near the edges of the cover plate to
unlock the plate, then remove the plate.
3.
Remove the DC power supply from its packaging.
4.
Insert the wires into the DC wiring assembly (Figure 3.2).
5.
Use the wire tightening screws to secure the wires.
Figure 3.2 The NetIron CES 2000 DC Power Supply
6.
With one hand, hold the bar on the front panel of the power supply. With the other hand, support the
underside of the power supply, and insert the power supply into the empty power supply slot. Press until the
supply is completely in the slot, so that the connectors on the back of the supply are fully engaged with the
pins on the power backplane.
CAUTION:
Make sure you insert the power supply right-side up. It is possible to insert the supply upside down,
although the supply will not engage with the power backplane when upside down. The power supply is right-side
up when the power connector is on the left and the fan vent is on the right. All references to right-side and left-side
are referenced from looking at the device from the front.
7.
Secure the two screws near the edges of the supply to lock the supply in place.
March 2009
Wire Tightening Screws
Assembly Screws
© 2009 Brocade Communications Systems, Inc.
Installation
3 - 7