Toshiba MMD-AP0726HP-UL Service Manual page 73

Multi type indoor unit
Table of Contents

Advertisement

Check codes Detected by TCC-LINK Central Control Device
Check code
Outdoor 7-segment display
Main
remote
control
Sub-code
C
0
5
C
0
6
C
1
2
Differs according to
nature of alarm-causing
trouble
P30
(L20 displayed.)
Location
of
Description
System status
detection
TCC-LINK TCC-LINK
Continued
central control
operation
device
transmission
trouble
TCC-LINK
Continued
central control
operation
device reception
trouble
Batch alarm
General-
Continued
purpose
for general-
operation
device
purpose device
I/F
control interface
TCC-LINK Group control
Continued
follower unit
operation
trouble
Duplicated
Continued
central control
operation
address
- 73 -
Trouble detection
Check items (locations)
condition(s)
Central control device is
• Check for defect in central
unable to transmit signal.
control device.
• Check for defect in central
control communication
line.
• Check termination
resistance setting.
Central control device is
• Check for defect in central
unable to receive signal.
control device.
• Check for defect in central
control communication
line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check defect in P.C.
boards of devices at other
end of central control
communication line.
Trouble signal is input to
• Check trouble input.
control interface for general-
purpose devices.
Trouble occurs in follower
• Check check code of unit
unit under group control.
that has generated alarm.
([P30] is displayed on central
control remote control.)
There is duplication in central
• Check address settings.
control addresses.

Hide quick links: