Toshiba MMD-AP0726HP-UL Service Manual page 30

Multi type indoor unit
Table of Contents

Advertisement

Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Filter display delay timer 0000: None
01
Dirty state of filter
02
Central control address 0001: No.1 unit
03
Specific indoor unit
04
priority
Heating temp shift
06
Existence of [AUTO]
0d
mode
Cooling only
0F
Type
10
Indoor unit capacity
11
12
Line address
13
Indoor unit address
Group address
14
Temp difference of
[AUTO] mode selection
1E
COOL → HEAT,
HEAT → COOL
Automatic restart of
28
power failure
Selection of option /
2A
trouble input (CN70)
HA terminal (CN61)
2E
select
31 Ventilating fan control
32 TA sensor selection
33 Temperature unit select 0000:
Static pressure selection
5d
Timer setting
60
(wired remote control)
External interlock
92
release condition
Whether the power
d0
saving mode can be set
by the remote control
77 Dual set point
Fd Priority operation mode
(Flow Selector unit)
FE Flow Selector unit
address
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
to
0099: Unfixed
0000: No priority
0000: No shift
(+3.6˚F)
to
0002: +2
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
* refer to
page Type CODE No. [10]
0000: Unfixed
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit of group
0000: 0 C (12˚F)
to
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0000: None
0000: Filter input
0002: None
0000: Usual
0002: Fire alarm input
0000: Unavailable
0000: Body TA sensor
Set data
0000
0.201 in.WG
External static
(Factory
pressure
default)
The list abpve is when SW501-1 and SW501-2 is OFF.
0000: Available (can be performed) 0001: Unavailable
0000: Operation stopped
0000: Invalid
0000: Unavailable
0000: Heating
0001: No.1 unit to 0064 : No.64 unit 0099: Unfixed
Description
0001: 150H
0003: 5000H
0064: No.64 unit
0001: Priority
(+1.8˚F)
0001: +1
0010: +10 C(+18˚F)
(Up to +6 recommended)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Header unit of group
0010: 10 C (18˚F)
0001: Restart
0001: Alarm input (Air washer, etc.) 0002: None
0001: Leaving-ON prevention control 0000: Usual
0001: Available
0001: Remote control sensor
0001: F (at factory shipment)
0001
0002
0.334 in.WG
0.470 in.WG
0.603 in.WG
(cannot be performed)
0001: Release signal received
0001: Valid
0002: Available
0001: Cooling
- 30 -
At shipment
According to type
0000: Standard
0099: Unfixed
0000: No priority
0002: +2 C(+3.6˚F)
0001: Not provided
0000: Heat pump
Depending on model
type
According to capacity
type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0003: 3 C (5.4˚F)
(Ts ±1.5 C)
0000: None
(HA terminal)
0000: Unavailable
0000: Body TA sensor
0001: F
0000: Standard
0003
0004
0005
0.735 in.WG
0.872 in.WG
0000: Available
0000: Operation
stopped
0001: Valid
0000: Unavailable
0000: Heating
0099: Unfixed
0006
1.005 in.WG