Toshiba MMD-AP0726HP-UL Service Manual page 70

Multi type indoor unit
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
control
code
P13
P13
01: TS condition
P15
P15
02: TD condition
P17
P17
Location
of
Description
System status
detection
I/F
Outdoor liquid
All stop
backflow
detection trouble
I/F
Gas
All stop
leakdetection
(TS1 condition)
I/F
Gas leak
All stop
detection
(TD condition)
I/F
Discharge
All stop
temperature
TD2 trouble
- 70 -
Trouble detection
Check items (locations)
condition(s)
<During cooling operation>
• Check full-close operation
When system is in cooling
operation, high pressure is
• Check for defect in Pd or
detected in follower unit that
Ps sensor.
has been turned off.
• Check gas balancing
<During heating operation>
circuit (SV2) for clogging.
When system is in heating
• Check balance pipe.
operation, outdoor PMV 1 or
• Check SV3B circuit for
3 continuously registers
clogging.
opening of 300p or less
• Check defect in outdoor
while under superheat
P.C. board (I/F).
control.
• Check capillary of oil
separator oil return circuit
for clogging.
• Check for leakage of check
valve in discharge pipe
convergent section.
Protective shutdown due to
• Check for insufficiency in
sustained suction
refrigerant quantity.
temperature at or above
• Check outdoor service
judgment criterion
valves (gas side, liquid
for at least 10 minutes is
side) to confirm full
repeated four times or more.
opening.
<TS trouble judgment
• Check PMVs (PMV1, 3) for
criterion> In cooling
clogging.
operation: 140°F(60°C) In
• Check resistance
heating operation: 104°F
characteristics of TS1
(40°C)
sensor.
• Check for defect in 4-way
valve.
• Check SV4 circuit for
leakage
Protective shutdown due to
• Check for insufficiency in
refrigerant quantity.
sustained discharge
• Check PMVs (PMV 1, 3)
temperature (TD1 or TD2)
at or above 226.4°F(108°C)
for clogging.
for at least 10 minutes is
• Check resistance
repeated four times or
characteristics of TD1 and
TD2 sensors.
more.
• Check indoor filter for
clogging.
• Check piping for clogging.
• Check SV4 circuit (for
leakage or coil installation
trouble).
Discharge temperature
• Check outdoor service
(TD2) exceeds
valves (gas side, liquid
239°F(115°C)
side) to confirm full
opening.
• Check outdoor PMVs
(PMV1, 3, 4) for clogging.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in 4-way
valve.
• Check SV4 circuit for
leakage.
• Check SV4 circuit (for
wiring or installation
trouble involving SV41
and SV42).
of outdoor PMV (1, 3, 4).

Hide quick links:

Advertisement

Table of Contents
loading