Toshiba MMD-AP0726HP-UL Service Manual page 67

Multi type indoor unit
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
control
code
L02
L02
L03
L04
L04
L05
No. of priority indoor units
L06
L06
L07
L08
L08
L09
L10
L10
L20
L23
L28
L28
Location
of
Description
System status
detection
Indoor
Outdoor units
Stop of
unit
model
corresponding
disagreement
unit
trouble
Indoor
Duplicated
Stop of
unit
indoor header
corresponding
unit
unit
I/F
Duplicated
All stop
outdoor line
address
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor
Connection of
Stop of
unit
group control
corresponding
cable to stand-
unit
alone indoor
unit
Indoor
Indoor group /
Stop of
unit
addresses not
corresponding
set
unit
Indoor
Indoor capacity
Stop of
unit
not set
corresponding
unit
I/F
Outdoor
All stop
capacity not set
Network
Duplicated
All stop
adaptor
central control
address
Indoor
unit
SW setting
I/F
All stop
mistake
I/F
Too many
All stop
outdoor units
connected
- 67 -
Trouble detection
Check items (locations)
condition(s)
In case of different outdoor
• Check outdoor unit model.
unit (Not corresponded to
(Check whether the
Air to Air Heat Exchanger
outdoor unit corresponds
type)
to Air to Air Heat
Exchanger type or not.)
There are more than one
Check indoor addresses.
Check for any change
header units in group.
made to remote control
connection (group/
individual) since indoor
address setting.
There is duplication in line
• Check line addresses.
address setting for outdoor
units belonging to different
refrigerant piping systems.
More than one indoor units
• Check display on priority
have been set up as priority
indoor unit.
indoor unit.
More than one indoor units
• Check displays on priority
have been set up as priority
indoor unit and outdoor
indoor unit.
unit.
There is at least one stand-
• Check indoor addresses.
alone indoor unit to which
group control cable is
connected.
Address setting has not been
• Check indoor addresses.
performed for indoor units.
Note:
Capacity setting has not been
Set indoor capacity. (DN =
performed for indoor unit.
11)
Jumper wire provided on P.C.
Check model setting of P.C.
board for servicing I/F P.C.
board for servicing outdoor
board has not been removed
I/F P.C. board.
as required for given model.
There is duplication in central
• Check central control
control address setting.
addresses.
• Check network adaptor
P.C. board .
Outdoor P.C. board (I/F)
Check switch setting of
does not operate normally.
Bit 3 and 4 of SW17 in
outdoor P.C. board (I/F).
There are more than three
• Check No. of outdoor units
connected (Only up to 3
outdoor units.
units per system allowed).
• Check communication
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).
This code is displayed
when power is turned on
for the first time after
installation.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd-ap0966hp-ul

Table of Contents