Toshiba MMD-AP0726HP-UL Service Manual page 54

Multi type indoor unit
Table of Contents

Advertisement

(Check code detected by IPDU featuring in SMMS-e standard outdoor unit - typical examples)
Check code
Outdoor 7-segment display
Sub-code
01: Compressor 1
F13
02: Compressor 2
01: Compressor 1
H01
02: Compressor 2
01: Compressor 1
H02
02: Compressor 2
01: Compressor 1
H03
02: Compressor 2
01: Compressor 1
P04
02: Compressor 2
01: Compressor 1
P07
02: Compressor 2
#0:Element short circuit
#1:Position detection circuit trouble
#3:Motor lock trouble
#4:Motor current trouble
#C:TH Sensor temperature trouble
P22
#D:TH Sensor short circuit/release
Trouble
#E:Vdc voltage Trouble
∗Put in Fan IPDU No. in [#] mark
01: Compressor 1
P26
02: Compressor 2
01: Compressor 1
P29
02: Compressor 2
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
Operation Timer Ready
Flash
control
display
F
1
3
A
L
T
H
0
1
H02
H03
P
0
4
A
L
T
P
0
7
A
L
T
P
2
2
A
L
T
P
2
6
A
L
T
P
2
9
A
L
T
- 54 -
Typical problem site
Trouble in temperature
Temperature sensor built into indoor IPM (TH)
sensor built into indoor
has been open/short-circuited.
IPM (TH)
Inverter current (Idc) detection circuit detects
C
o
m
p
e r
s s
r o
b
e r
a
k
d
o
w
n
overcurrent.
Compressor trouble
Compressor lockup is detected
(lockup)
Current detection circuit
Abnormal current is detected while inverter
trouble
compressor is turned off.
Activation of high-pressure
High-pressure SW is activated.
SW
Temperature sensor built into IPM (TH) detects
Heat sink overheating
trouble
overheating or has been short-circuited.
Outdoor fan IPDU trouble
Outdoor fan IPDU detects trouble.
Short-circuit protection for compressor motor
Activation of IPM
driver circuit components is activated (momentary
short-circuit protection
overcurrent).
Compressor motor position detection trouble is
Compressor position
detection circuit trouble
detected.
Description of proplem

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd-ap0966hp-ul

Table of Contents