Toshiba MMD-AP0726HP-UL Service Manual page 45

Multi type indoor unit
Table of Contents

Advertisement

< Based on the SMMS-e >
CODE No.
Data name
00
Room temperature (Use to control)
01
Room temperature (Remote control)
02
Indoor suction air temperature (TA)
03
Indoor coil temperature (TCJ)
04
Indoor coil temperature (TC2)
05
Indoor coil temperature (TC1)
06
Indoor discharge air temperature (TF) *
08
Indoor PMV opening
F3
Filter sign time
Suction temperature of air to air heat
F9
exchanger (TSA) *
FA
Outside air temperature (TOA)*
0A
No. of connected indoor units
0B
Total horsepower of connected indoor units
0C
No. of connected outdoor units
0D
Total horsepower of outdoor units
CODE No.
U1
U2
U3
10
20
30
High-pressure sensor detention pressure (Pd)
11
21
31
Low-pressure sensor detention pressure (Ps)
12
22
32
Compressor 1 discharge temperature (TD1)
13
23
33
Compressor 2 discharge temperature (TD2)
15
25
35
Outdoor coil temperature (TE1)
16
26
36
Outdoor coil temperature (TE2)
17
27
37
Outdoor coil temperature (TG1)
18
28
38
Outdoor coil temperature (TG2)
19
29
39
Outside ambient temperature (TO)
1A
2A
3A
Suction temperature (TS1)
3C
Suction temperature (TS3)
1C
2C
1D
2D
3D
Temperature at liquid side (TL1)
1E
2E
3E
Temperature at liquid side (TL2)
1F
2F
3F
Temperature at liquid side (TL3)
CODE No.
U1
U2
U3
50
60
70
PMV1 opening
51
61
71
PMV3 opening
52
62
72
PMV4 opening
1 fan model : Compressor 1 curent (I1)
53 63 73
2 fan model : Compressor 1 and Outdoor fan 1 current (I1)
1 fan model : Compressor 2 and Outdoor fan 1 current (I2)
54 64 74
2 fan model : Compressor 2 and Outdoor fan 2 current (I2)
56
66
76
Compressor 1 revolutions
57
67
77
Compressor 2 revolutions
59
69
79
Outdoor fan mode
5A
6A
7A
Compressor IPDU 1 heat sink temperature
5B
6B
7B
Compressor IPDU 2 heat sink temperature
5D
6D
7D
Outdoor fan IPDU 1 heat sink temperature
Outdoor fan IPDU 2 heat sink temperature
5E
6E
7E
5F
6F
7F
Outdoor unit horsepower
CODE No.
90
Heating/cooling recovery controlled
91
Pressure release
92
Discharge temperature release
93
Follower unit release (U2/U3 outdoor units)
*1 Only a part of indoor unit types is installed with the discharge air temperature sensor. This temperature is
not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1
, 5
... U1 outdoor unit (Header unit)
2
, 6
... U2 outdoor unit (Follower unit 1)
3
, 7
... U3 outdoor unit (Follower unit 2)
*5 Only the CODE No. 9* of U1 outdoor unit (Header unit) is displayed.
1
1
1
Data name
Data name
Data name
Display format Unit
×1
×1
×1
×1
×1
×1
×1
×1/10
×1
×1
×1
×1
×10
×1
×10
Display format Unit
×10
×10
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
Display format Unit
×1
×1
×1
×10
×10
×10
×10
×1
×1
×1
×1
×1
×10
Display format Unit
0: Normal
[0010]=Heating recovery controlled
[0010]=Pressure release controlled
0: Normal
[0001]=Discharge temperature release controlled
1: Release controlled
[0100]=U2 outdoor unit release controlled
- 45 -
Remote control display example
°C
[0027] = 27 °C
°C
°F
°F
[0075]= 75 °F
°F
°F
°F
pls
[0150]= 1500 pls
h
[2500] = 2500h
°F
[0080]= 80 °F
°F
unit
[0048]= 48 units
ton
[0215]= 21.5 ton
unit
[0003]= 3 units
ton
[0160]= 16 ton
Remote control display example
psi
[4350] = 435 psi
psi
°F
°F
°F
°F
°F
[0075]= 75 °F
°F
°F
°F
°F
°F
°F
°F
Remote control display example
pls
pls
[0500] = 500pls
pls
A
[0135] = 13.5A
A
rps
[0642] = 64.2rps
rps
mode
[0058] = 58 mode
°F
°F
[0075]= 75 °F
°F
°F
ton
[0080] = 8 ton
Remote control display example