Toshiba MMD-AP0726HP-UL Service Manual page 60

Multi type indoor unit
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
control
code
Duplicated indoor address
E08
E08
E09
E10
Communication
trouble between
Application control
kit and indoor unit
E11
01:
Indoor-outdoor
communication
02:
Outdoor-outdoor
E12
E12
communication
E15
E15
00:
Overloading
01-:
No. of units connected
E16
E16
Location
of
Description
System status
detection
Indoor
Duplicated
All stop
unit
indoor address
I/F
Remote
Duplicated
Stop of
control
master remote
corresponding
control
unit
UART
Indoor
Stop of
unit
corresponding
communication
trouble
unit
Stop
Indoor
Indoor
unit
Application
control P.C.Board
communication
trouble
I/F
Automatic
All stop
address starting
trouble
I/F
Indoor unit not
All stop
found during
automatic
address setting
I/F
Too many
All stop
indoor units
connected
- 60 -
Trouble detection
Check items (locations)
condition(s)
More than one indoor unit
Check indoor addresses.
are assigned same address.
Check for any change
made to remote control
connection (group/
individual) since indoor
address setting.
In two remote control
• Check remote control
configuration (including
settings.
• Check remote control
wireless), both control are set
P.C. Boards.
up as master. (Header
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Communication cannot be
• Check for defect in indoor
established/maintained upon
P.C. Board
turning on of power or during
(MCC-1643 and MCC-1610)
communication.
Displayed when trouble is
1.
Check connector indoor
unit (CN521(red))
detected
Application control
P.C.Board (CN1 (red))
2.
Check connection of
indoor-Application control
kit communication line.
3. Check indoor P.C. Board.
4. Check Application control
P.C. Board.
• Indoor automatic address
• Perform automatic address
setting is started while
setting again after
automatic address setting
disconnecting
for equipment in other
communication cable to
refrigerant line is in
that refrigerant line.
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
Indoor unit cannot be
• Check connection of
indoor-outdoor
detected after indoor
communication line.
automatic address setting is
• Check for trouble in indoor
started.
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for defect in indoor
P.C. Board.
• Combined capacity of
• Check capacities of indoor
indoor units exceeds 135%
units connected.
of combined capacity of
• Check combined HP
capacities of indoor units.
outdoor units.
• Check HP capacity
Note:
settings of outdoor units.
If this code comes up
• Check No. of indoor units
after backup setting for
connected.
outdoor unit failure is
• Check for defect in outdoor
performed, perform "No
P.C. Board (I/F).
overloading detected"
setting.
<"No overloading detected"
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
• More than 64 indoor units
are connected.