Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
control
code
#0:Element short circuit
#1:Position detection circuit
trouble
#3:Motor lock trouble
P22
P22
#4:Motor current trouble
#C:TH sensor
temperature trouble
#D:TH sensor short
circuit/release trouble
#E:Vdc voltage trouble
01: Compressor 1 side
02: Compressor 2 side
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
P31
Location
of
Description
System status
detection
Outdoor fan
IPDU
All stop
IPDU trouble
*Put in Fan
IPDU No. in [#]
mark
All stop
All stop
All stop
All stop
All stop
All stop
IPM short-
IPDU
All stop
circuit protection
trouble
IPDU
Compressor
All stop
position
detection circuit
trouble
Indoor
Other indoor
Stop of
trouble
unit
corresponding
(group follower
unit
unit trouble)
- 72 -
Trouble detection
Check items (locations)
condition(s)
(Sub code: #0)
Fan IPDU over current
Check fan motor.
protection circuit
Check for defect in fan IPDU
Flow of current equal to or
P.C. board.
greater than the specified
value is detected during
startup of the fan.
(Sub code: #1)
• Check fan motor.
• Check connection of fan
Fan IPDU position
motor connector.
detection circuit Position
• Check for defect in fan IPDU
detection is not going on
P.C. board.
normally.
(Sub code: #3)
Gusty wind, an obstruction,
Check fan motor.
or another external factor
Check for defect in fan IPDU
Speed estimation is not
P.C. board.
going on normally.
(Sub code: #4)
• Check fan motor.
Fan IPDU over current
• Check connection of fan
protection circuit
motor connector.
Flow of current equal to or
• Check for defect in fan IPDU
greater than the specified
P.C. board.
value is detected during
operation of the fan.
(Sub code: #C)
Higher temperature than
• Check fan motor.
the specified value is
• Check for defect in fan IPDU
detected during operation
P.C. board.
of the fan.
(Sub code: #D)
Check for defect in fan
The resistance value of
IPDU P.C. board.
the sensor is infinite or
zero (open or short circuit).
Check power voltage of
(Sub code: #E)
the main power supply.
Fan IPDU DC voltage
Check for defect in fan IPDU
protection circuit
P.C. board.
The DC voltage higher or
Check connection of fan
lower than the specified
IPDU P.C. board.
value is detected.
Overcurrent is momentarily
• Check connector
detected during startup of
connection and wiring on
compressor.
A3-IPDU P.C. board.
• Check for defect in
compressor (layer short-
circuit).
• Check for defect in
outdoor P.C. board (A3-
IPDU).
Position detection is not
• Check wiring and
going on normally.
connector connection.
• Check for compressor
layer short-circuit.
• Check for defect in A3-
IPDU P.C. board.
There is trouble in other
• Check indoor P.C. board.
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.