4.1

Rules of System Configuration

The system configuration must meet the following four requirements.
Number of connected extension device
The number of extension devices that can be connected to a single system of FX5U CPU module is limited.
For details, refer to Page 62 Limitations on the Number of Connected Extension Devices.
Ex.
Expansion
Expansion
adapters
adapters
(Commu-
(Analog)
nication)
Up to 4
Up to 2
modules
modules
*1 Extension power supply modules and connector conversion module are not included in the number of connected devices.
Number of input/output points
With the FX5U CPU module, a total of 512 points or less including the number of input/output points of extension devices
(max. 256 points) and number of remote I/O points (max. 384 points) can be controlled.
For details on the number of input/output points, refer to Page 65 Limitation on the Number of Input/Output Points.
4 SYSTEM CONFIGURATION
60
4.1 Rules of System Configuration
CPU module
Input
FX5
module,
Expansion
Intelligent
Output
board
module
module
Up to 8
Up to 1
modules
module
Up to 12 modules
Extended extension cable
Up to 1 cable
FX5
Input
extension
module,
power
Output
supply
module
module
Up to 10 modules
Up to 16 modules
*1
FX3
Bus
FX5
extension
power
Intelligent
conversion
supply
module
module
module
Up to 1
module
Up to 8 modules
Up to 2 modules
FX3
Intelligent
module
Up to 8
modules